XALD213 Schneider Control Station
- Product or component type: complete control station
- Operator profile: 2 flush push-buttons
- 1 button red 1 NC '0' marking
- 1 button green 1 NO 'I' marking
- Contacts operation: slow-break
- Colour of base of enclosure: light grey RAL 7035
- Colour of cover: dark grey RAL 7016
- Material: polycarbonate
- Product range: Harmony XALD
- Schneider Electric type XALD213
Product Description
A complete start/stop control station with two 22mm diameter flush push-buttons.
Technical Specification
- Range of product: Harmony XALD
- Product or component type: Complete control station
- Device short name: XALD
- Product destination: For XB5 22 mm control and signalling units
- Control station application: Start-Stop function
- Colour of base of enclosure: Light grey RAL 7035
- Colour of cover: Dark grey RAL 7016
- Material: Polycarbonate
- Operator profile: 2 flush push-buttons
- Operators description: Green ''I'' 1 NO - red ''O'' 1 NC
- Control station composition:
- 1 flush push-button green 1 NO I marking
- 1 flush push-button red 1 NC O marking
- Marking location Marking on push-button
- Contact operation Slow-break
Complementary:
- Cable Entry:
- 2 knock-outs for cable entry, clamping capacity: 14 mm
- 2 knock-outs for Pg 13 cable gland and ISO M20, clamping capacity: 12 mm
- Product weight 0.233 kg
- Resistance to high pressure washer 7000000 Pa at 55 °C, distance: 0.1 m
- Mechanical durability 10000000 cycles
- Colour of marking:
- Black marking when white caps
- White marking when green, red or black caps
- Positive opening: With conforming to EN/IEC 60947-5-1 appendix K
- Operating travel:
- 1.5 mm (NC changing electrical state)
- 2.6 mm (NO changing electrical state)
- 4.3 mm (total travel)
- Connections - terminals:
- Screw clamp terminals : <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1
- Screw clamp terminals : >= 1 x 0.22 mm² without cable end conforming to EN/IEC 60947-1
- Tightening torque: 0.8...1.2 N.m conforming to EN/IEC 60947-1
- Shape of screw head:
- Cross, Philips no 1
- Cross, pozidriv No 1
- Slotted, flat Ø 4 mm
- Slotted, flat Ø 5.5 mm
- Short-circuit protection: 10 A by gG cartridge fuse conforming to EN/IEC 60947-5-1
- [Ith] conventional free air thermal current: 10 A conforming to EN/IEC 60947-5-1
- [Ui] rated insulation voltage: 600 V (degree of pollution: 3) conforming to EN/IEC 60947-1
- [Uimp] rated impulse withstand voltage: 6 kV conforming to EN/IEC 60947-1
- [Ie] rated operational current:
- AC-15, A600: Ue = 120 V Ie = 6 A conforming to EN/IEC 60947-5-1
- AC-15, A600: Ue = 240 V Ie = 3 A conforming to EN/IEC 60947-5-1
- AC-15, A600: Ue = 600 V Ie = 1.2 A conforming to EN/IEC 60947-5-1
- DC-13, Q600: Ue = 125 V Ie = 0.55 A conforming to EN/IEC 60947-5-1
- DC-13, Q600: Ue = 250 V Ie = 0.27 A conforming to EN/IEC 60947-5-1
- DC-13, Q600: Ue = 600 V Ie = 0.1 A conforming to EN/IEC 60947-5-1
- Electrical reliability:
- ? < 10exp(-6) at 5 V, 1 mA conforming to EN/IEC 60947-5-4
- ? < 10exp(-8) at 17 V, 5 mA conforming to EN/IEC 60947-5-4
- Standards:
- EN/IEC 60947-5-1
- EN/IEC 60947-5-5
- JIS C 4520
- EN/IEC 60947-1
- UL 508
- EN/IEC 60947-5-4
- CSA C22.2 No 14
- Vibration resistance: 5 gn (12...500 Hz) conforming to IEC 60068-2-6
- Shock resistance:
- 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
- 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27