VCF2GE Schneider Isolator Electric
Technical Specification
- Range: TeSys
- Device short name VCF
- Product or component type: Emergency stop switch disconnector
- Performance level: High performance
- Poles description: 3P
- Control type: Rotary handle
- Handle colour: Red
- Handle front plate colour: Yellow
- Rotary handle padlocking: 1 to 3 padlocks with 4...8 mm
Complementary
- Marking: 0 - 1
- [Ue] rated operational voltage: 690 V AC
- [Uimp] rated impulse withstand voltage: 8 kV
- [Ithe] conventional enclosed thermal current: 32 A
- [Ie] rated operational current: 14.5 A AC-23A at 400 V
- Rated operational power in W:
- 11 kW at 400 V AC-3
- 15 kW at 400 V AC-23
- Intermittent duty class 30
- Icm] rated short-circuit making capacity 1 kA at 400 V at Ipeak
- [Icw] rated short-time withstand Rms current: 480 A at 400 V during 1 s
- Breaking capacity:
- 320 A at 400 V (AC-21A)
- 320 A at 400 V (AC-22A)
- 320 A at 400 V (AC-23A)
- Mechanical durability 100000 cycles
- Environmental characteristic: Standard environment
- Tightening torque 2.1 N.m - on screw clamp terminals
- Fire resistance 960 °C conforming to IEC 60595-2-1
- Handle front plate dimension: 60 x 60 mm
- Height: 146 mm
- Width: 90 mm
- Depth: 131 mm
- Product weight: 0.5 kg
- Standards:
- IEC 60947-4-1
- IEC 60204
- Ambient air temperature for operation: -20...50 °C