RXM4AB2BD Schneider Mini Relay+LED Electric
Pack of 10
- Rated current 6A
- Status LED
- Lockable test button
- Easy installation and maintenance
- Standards IEC, UL, CSA
- Dimensions 27 x 21 x 40mm
Product Description
A 24V DC 4PDT relay from the Schneider Electric Zelio RMX series. This miniature plug-in relay has 4x changeover contacts and is ideal for use in industrial machines, building machinery, medical equipment, packaging machines, textile machines, HVAC, etc.
Technical Specification
- Range of product: Zelio Relay
- Series name: Miniature
- Product or component type: Plug-in relay
- Device short name: RMX
- Contacts type and composition: 4 C/O
- [Uc] control circuit voltage: 24 V DC
- [Ithe] conventional enclosed thermal current: 6 A at -40...55 °C
- Status LED: With
- Control type: Lockable test button
- Utilisation coefficient: 20 %
Complementary
- Shape of pin: Flat
- [Ui] rated insulation voltage:
- 250 V conforming to IEC
- 300 V conforming to UL
- 300 V conforming to CSA
- [Uimp] rated impulse withstand voltage 2.5 kV for 1.2/50 µs
- Contacts material AgNi
- [Ie] rated operational current 3 A at 28 V DC (NC) conforming to IEC:
- 3 A at 250 V AC (NC) conforming to IEC
- 6 A at 28 V DC (NO) conforming to IEC
- 6 A at 250 V AC (NO) conforming to IEC
- 6 A at 277 V AC conforming to UL
- 8 A at 30 V DC conforming to UL
- Maximum switching voltage 250 V conforming to IEC
- Maximum switching capacity 1500 VA/168 W
- Minimum switching capacity 170 mW at 10 mA, 17 V
- Mechanical durability 10000000 cycles
- Electrical durability 100000 cycles for resistive load
- Average coil consumption in W 0.9 W
- Drop-out voltage threshold >= 0.1 Uc
- Operate time 20 ms
- Release time 20 ms
- Average coil resistance 650 Ohm at 20 °C +/- 10 %
- Rated operational voltage limits 19.2...26.4 V DC
- Safety reliability data B10d = 100000
- Standards:
- EN/IEC 61810-1
- UL 508
- CSA C22.2 No 14
- Vibration resistance:
- 3 gn (f = 10...150 Hz), amplitude +/- 1 mm (on 5 cycles in operation)
- 5 gn (f = 10...150 Hz), amplitude +/- 1 mm (on 5 cycles not operating)
- IP degree of protection IP40 conforming to EN/IEC 60529
- Shock resistance:
- 10 gn in operation
- 30 gn not operating
- Pollution degree 2