Schneider Relay 16?24a LRD22

Schneider Electric Relay 16-24A - LRD22

Regular price
Rs. 34.32
Sale price
Rs. 34.32
Regular price
Sold out
Unit price
per 

LRD22 Schneider Relay Electric

  • Class 10A overload tripping
  • Screw terminals
  • Flame retardance conforms to UL 94

Product Description

A 16 to 24A differential thermal overload relay from the TeSys LRD series. The relay is controlled via Start and Stop push-buttons. Designed for motor protection applications.

Technical Specification 

  • Range: TeSys
  • Product name: TeSys LRD
  • Product or component type: Differential thermal overload relay
  • Device short name: LRD
  • Relay application: Motor protection
  • Product compatibility:
    • LC1D25
    • LC1D32
    • LC1D38
  • Network type:
    • DC
    • AC
  • Thermal protection adjustment range 16...24 A

Complementary: 

  • Network frequency 0...400 Hz
  • [Ue] rated operational voltage 690 V AC 0...400 Hz
  • [Uimp] rated impulse withstand voltage 6 kV
  • Phase failure sensitivity Tripping current 130 % of Iron two phases, the last one at 0
  • Width: 45 mm
  • Depth: 70 mm
  • Product weight: 0.124 kg
    • Protective treatment TH conforming to IEC 60068
    • IP degree of protection IP20 conforming to IEC 60529
    • Ambient air temperature for operation -20...60 °C without derating conforming to IEC 60947-4-1
    • Ambient air temperature for storage -60...70 °C
    • Flame retardance V1 conforming to UL 94
    • Mechanical robustness:
      • Vibrations 6 Gn IEC 60068-2-6
      • Shocks 15 Gn for 11 ms IEC 60068-2-7
      • Dielectric strength 6 kV at 50 Hz conforming to IEC 60255-5
    • Standards:
      • IEC 60947-5-1
      • ATEX D 94/9/CE
      • IEC 60947-4-1
      • EN 60947-4-1
      • UL 508
      • EN 60947-5-1
      • CSA C22.2 No 14>

    Downloads

    LRD22 Instructions

    LRD22 Datasheet