| circuit breaker application |
Distribution
|
|
|---|---|---|
| range |
Acti 9
|
|
| product name |
Acti 9 iC60 RCBO
|
|
| product or component type |
Residual current breaker with overcurrent protection (RCBO)
|
|
| device short name |
IC60N RCBO
|
|
| poles description |
1P + N
|
|
| [In] rated current |
40 A at 30 °C
|
|
| curve code |
C
|
|
| earth-leakage sensitivity |
30 mA
|
|
| breaking capacity |
Icn : 10000 A - 150...230 V - AC at 50 Hz
|
| neutral position |
Left
|
|
|---|---|---|
| number of protected poles |
1
|
|
| network type |
AC
|
|
| network frequency |
50 Hz
|
|
| [Ue] rated operational voltage |
Ue: 150...230 V - AC at 50 Hz
|
|
| trip unit technology |
Thermal-magnetic
|
|
| residual current tripping technology |
Voltage dependent
|
|
| earth-leakage protection time delay |
Instantaneous
|
|
| earth-leakage protection class |
Type A
|
|
| [Icw] rated short-time withstand current |
Icw: 250 A during 8/20 µs impulse withstand
|
|
| electrical insulation class |
Class III
|
|
| limitation class |
3
|
|
| [Ui] rated insulation voltage |
Ui: 400 V - AC at 50 Hz
|
|
| [Uimp] rated impulse withstand voltage |
Uimp: 4 kV
|
|
| suitability for isolation |
Yes
|
|
| contact position indicator |
Yes
|
|
| control type |
Toggle
|
|
| local signalling |
ON/OFF indication
|
|
| mounting mode |
Clip-on
|
|
| mounting support |
DIN rail
|
|
| comb busbar and distribution block compatibility |
YES
|
|
| 9 mm pitches |
2
|
|
| height |
93 mm
|
|
| width |
18 mm
|
|
| depth |
70 mm
|
|
| product weight |
136 g
|
|
| colour |
White
|
|
| mechanical durability |
20000 cycles
|
|
| electrical durability |
10000 cycles
|
|
| provision for padlocking |
Padlockable
|
|
| locking options description |
By padlocks
|
|
| connections - terminals |
Screw clamp terminal connection on upstream - 1...16 mm² - rigid
Screw clamp terminal connection on upstream - 1...16 mm² - flexible Screw clamp terminal connection on downstream - 1...10 mm² - rigid Screw clamp terminal connection on downstream - 1...10 mm² - flexible |
|
| wire stripping length |
14 mm on upstream of
11 mm on downstream of |
|
| tightening torque |
2 N.m on upstream of
2 N.m on downstream of |
|
| earth-leakage protection |
Integrated
|
|
| targeted country |
UK
|
| standards |
IEC 61009-1
IEC 61009-2-2 |
|
|---|---|---|
| product certifications |
SNI
|
|
| IP degree of protection |
IP20
|
|
| tropicalisation |
2
|
|
| relative humidity |
95 % at 55 °C
|
|
| ambient air temperature for operation |
-25...55 °C
|
|
| ambient air temperature for storage |
-30...70 °C
|